Scaling
The following figure illustrates the relationship between the input current
measured at the field terminals and the data that is output by the module.
Note 1) 4-20mA Range
4.000mA
0
The following equations can be used to calculate count values:
4-20mA Range:
0-20mA Range:
Note 1: In 4-20mA mode, signal inputs below 4.077mA are converted to zero counts.
Note 2: In 4-20mA mode, signal inputs at 20.000mA or above 20.383mA are
converted to 32000 counts.
Operating Range
GFK-1504N
Chapter 10 Analog Input Modules
Analog Input Module, 15 Bit Differential Current 8 Channels
4-20mA Range
0.5µA = 1counts
12.1925mA
4.077mA
154
12.192mA
16384
4.0765mA
0
24
mA
20
16
12
8
4
0
0
8192
Counts = (Current in mA - 4mA) x (32000 / 16mA
Counts = (Current in mA ) x (32000 / 20mA
Note 2) 4-20mA Range
12.1935mA
12.193mA
16386
16385
20.000mA
32000
16384
24576
32767
Count
10
IC200ALG262
20.3835mA
32767
20.384mA
32000
0-20mA Range
0.625µA = 1counts
10.241875mA
10.24125mA
16386
10.240625mA
16385
10.240mA
16384
)
)
10-33