GE VersaMax IC200PWR001 User Manual page 172

Table of Contents

Advertisement

Module Specifications
Module Characteristics
Points
Module ID
Isolation:
User input to logic (optical)
and frame ground
Group to group
Point to point
LED indicators
Backplane current
consumption
External power supply
Thermal derating
Compatibility
HW,FW vers.
FW release
Input Characteristics
Input voltage
On state voltage
Off state voltage
On state current
Off state current
On response time
Off response time
Input impedance
GFK-1504N
Chapter 7 Discrete Input Modules
16 inputs (2 groups of 8)
88048804
250 V AC continuous; 1500 V AC for 1 minute
250 V AC continuous; 1500 V AC for 1 minute
None
One LED per point shows individual point ON/OFF status
OK LED indicates backplane power is present
5 V output: 110 mA maximum
None
Refer to associated diagram.
Cimplicity
VersaPro
Control
ME
90
2.11
1.0
2.2
0 to 264 V AC (47 to 63Hz), 240 V AC nominal
155 to 264 V AC
0 to 40 V AC
7 mA minimum
1.5 mA maximum
1 cycle maximum
2 cycles maximum
38.5 kΩ (reactive) at 60Hz, typical
46.3 kΩ (reactive) at 50Hz, typical
Input Module, 240 V AC16 Points
CPU
CPU
CPU
CPU
001
002
005
E05
AA
AA
AA
AA
1.0
1.5
2.1
2.1
7
IC200MDL241
DBI
EBI
GBI
PBI
001
001
001
001
AA
AA
AA
AA
1.1
1.0
1.0
1.0
7-19