3. Wiring

Molded-Case Circuit Breaker / Magnetic Contact

GE Power Controls maintenance and service do not apply to damage caused by
following situation:
(1) Damage to the inverter caused by the lack of appropriate molded-case circuit breaker
or a circuit breaker with too-large capacity is installed in between the power supply and
the inverter.
(2) Damage to the inverter caused by the serial magnetic contactor, phase advancing
capacitor, or surge-protector in between the inverter and the motor.
Model No: U20N
Molded-case circuit breaker line
Made by GE
Magnetic Contact
(MC)
Primary Circuit Terminal (TM1)
L1
L2
T1
T2
Signal Terminal (TM2)
1~11

Please utilize three-phase squirrel-cage induction motor with appropriate capacity.

If a inverter is used to drive more than one motor, the total capacity must be smaller
than the capacity of the inverter. Additional thermal relay must be installed in front of
every motor. Use the Fn_18 at 1.0 times of the rated value specified on the motor
nameplate at 50Hz, 1.1 times of the rated value specified on the motor nameplate at
60Hz.

Do not install phase advancing capacitor, LC, or RC component between the inverter
and the motor.
0K2S 0K4S 0K7S
20A
Made by GE
CL00
Wire dimension
2
2.5mm
Terminal screw M3
T3
Wire dimension 0.75mm
1K5S
30A
Made by GE
CL00
Wire dimension
2
2.5mm
Terminal screw M3
2
(#18 AWG), Terminal screw M3
8
2K2S
30A
Made by GE
CL00
Wire dimension
2
2.5mm
Terminal screw M3