IC200ALG325
Analog Output Module, 13 Bit Voltage 8 Channels
Jumper Selection
Jumpers on the carrier can be used to select the output range and output
default mode.
Range Jumper
If no jumper is installed on pins B1 and B2, outputs are configured for the
bipolar range of –10 to +10 V. With a jumper installed, the outputs are
configured for the unipolar range of 0 V to +10 V.
Hold Jumper
If no jumper is installed on pins B2 and B3, outputs hold their last state (the last
commanded value from the backplane) if backplane power or communications
are interrupted or the PLC is stopped. With a jumper installed, outputs default
to 0 V. This should only be changed with the field power and backplane power
removed.
Wiring Example
11-24
VersaMax Modules, Power Supplies and Carriers User's Manual
Range Jumper (JMP 1)
None
Installed
Hold Jumper (JMP 2)
None
Installed
Jumper installed = unipolar range
no jumper = bipolar range
Jumper installed = default to 0V
no jumper = hold last state
Load 1
Load 2
-
+
Range
-10 to +10 V
0 to +10 V
Output Default
Hold Last State
0 V
JMP 1
RET
JMP 2
Shield
V OUT 1
Return 1, 2
V OUT 2
Shield
Field Return
Field Power
GFK-1504N