GE VersaMax IC200PWR001 User Manual page 439

Table of Contents

Advertisement

Analog Mixed Module, 12 Bit ± 10 V DC Input 4 Channels and Output 2 Channels
Scaling
The following graphs illustrate the relationship between the voltage applied at
the field terminals and the data values for the module.
Count vs Input Voltage
Voltage
12
10
8
6
4
2
0
-2
-4
-6
-8
-10
-12
0
The following equation can be used to calculate counts values:
Counts = (Voltage In) x (3200)
The count value is returned as a multiple of 8. A voltage that would return a
count value (using the above equation) that is not a multiple of 8 will return the
next highest multiple of 8.
GFK-1504N
Chapter 12 Analog Mixed I/O Modules
8192
16384
24576
Count
Input Voltage
Count
5.1200
16384
5.1210
16392
5.1220
16392
5.1225
16392
8 counts =
2.5mV
5.125V
5.1225V
5.12V
16392
16384
32767
12
IC200ALG432
5.1275V
16408
16400
12-23