IC200ALG322
Analog Output Module, 12 Bit Voltage -10 to +10 V DC 4 Channels
Module Specifications
Module Characteristics
Channels
Module ID
Isolation:
User input to logic (optical)
and to frame ground
Group to group
Channel to channel
LED indicators
Backplane current consumption
Thermal derating
Configuration parameters
Diagnostics
Compatibility
HW, FW vers.
FW release
External Power Supply
Recommended range
Current consumption at
recommended range
12V operation range
Current consumption at 12V range 210mA max.(including load current)
Output Characteristics
Output voltage
Load characteristics:
Accuracy at 25 °C
Accuracy at 0 to 60 °C
Resolution
Update rate per module
Channel-to-channel crosstalk
rejection
Output default
In the presence of severe RF interference, (IEC 1000-4-3, 10V/m),
accuracy may be degraded to ±1%.
11-16
VersaMax Modules, Power Supplies and Carriers User's Manual
PME programming
software
All
Resistive
Capacitive
4 single-ended, one group
FFFF9040
250 V AC continuous; 1500 V AC for 1 minute
Not applicable
None
FLD PWR LED indicates field power is present
OK LED indicates backplane power is present
5V output: 50mA maximum
None
Output default
Loss of User Side Power
CPU
CPU
CPU
CPU
001
002
005
E05
AA
AA
AA
AA
1.0
1.5
2.1
2.1
+18 to +30 V DC (including ripple)
160mA max.(including load current)
9.6 to 15 V DC, 12 V DC nominal (including ripple)
±10.24 V DC
5000 Ω minimum
1.0µF maximum
± 0.3% typical of full scale, ± 0.5% max of full scale
±1% maximum of full scale
5mV = 16 counts
0.3ms maximum
70dB minimum
Hold Last State (default), 0 (configurable)
DBI
EBI
GBI
PBI
001
001
001
001
AA
AA
AA
AA
1.1
1.0
1.0
1.0
GFK-1504N