Discrete output module IC200MDL743 provides one group of 16 discrete
outputs. The outputs are negative or sinking type outputs. They switch the loads
to the negative (return) side of the DC supply and thus receive current from the
loads.
Q
1
An external DC power supply must be provided to switch power to the loads.
Intelligent processing for this module is performed by the CPU or NIU. The
module receives 16 bits of discrete output data.
LED Indicators
Individual green LEDs indicate the on/off state of the output points. The LEDs
are powered from the backplane. LED operation is dependent on the
application of valid field power, but independent of load conditions.
The green FLD PWR LED is ON when field power is applied to the module.
The green OK LED is ON when backplane power is present to the module.
GFK-1504N
Chapter 8 Discrete Output Modules
Output Module, 5/12/24 V DC Negative Logic 0.5 A, 16 Points
2
3
4
5
6
7
8
9
10 11 12 13 14 15 16
IC200MDL743
FLD
PWR
OK
IC200MDL743
OUTPUT
5/12/24VDC
NEG GRP
.5A
16PT