Module Specifications
Module Characteristics
Channels
Module ID
Isolation:
User input to logic (optical) and to
frame ground
Group to group
Channel to channel
LED indicators
Backplane current consumption
Thermal derating
Configuration parameter
Diagnostics
Compatibility
HW, FW vers.
FW release
External Power Supply
Recommended range
Current consumption at recommended
range
12V operation range
Current consumption at 12V range
Output Characteristics
Output current
Load characteristics:
Resistive
Capacitive
Inductive
Accuracy at 25 °C
Accuracy at 0 to 60 °C
Resolution
Update rate per module
Channel-to-channel crosstalk rejection 70dB minimum
Output default
In the presence of severe RF interference, (IEC 1000-4-3, 10V/m), accuracy may be degraded
to ±1%.
††
R
= (V
L(MAX)
GFK-1504N
Chapter 11 Analog Output Modules
Analog Output Module, 12 Bit Current, 4 Channels
4 single-ended, one group
FFFF9440
250 V AC continuous; 1500 V AC for 1 minute
Not applicable
None
FLD PWR LED indicates field power is present
OK LED indicates backplane power is present
5V output: 50mA maximum
Refer to associated diagram
Output default
Loss of User Side Power
PME programming
software
All
+18 to +30 V DC (including ripple)
160mA max (including load current)
9.6 to 15 V DC, 12 V DC nominal (including ripple)
240mA max (including load current)
4 to 20mA
0 to 1250 Ω maximum
0.1µF maximum
0.5H maximum
± 0.3% typical of full scale, ± 0.5% max. of full scale
±1% maximum of full scale
4µA = 8 counts
0.3ms maximum
Hold Last State (default), 4mA (configurable)
– 4V) / 20.38mA
EXTERNAL PS
CPU
CPU
CPU
CPU
001
002
005
E05
AA
AA
AA
AA
1.0
1.5
2.1
2.1
††
11
IC200ALG320
DBI
EBI
GBI
PBI
001
001
001
001
AA
AA
AA
AA
1.1
1.0
1.0
1.0
11-3