12
Analog Mixed Module, 12 Bit 0 to 10 V DC Input 4 Channels and Output 2 Channels
Count vs Output Voltage
Voltage
12
11
10
9
8
7
6
5
4
3
2
1
0
0
3200 6400 9600 12800 16000
Voltage can be calculated using the following equation:
V
= ( (analog counts x 10.25) / 32768 )
out
The count value must be a multiple of 8. If the module receives a count value
that is not a multiple of 8, it rounds the value down to the closest multiple of 8.
For example:
12-16
VersaMax Modules, Power Supplies and Carriers User's Manual
19200 22400 25600 28800 32000
Count
Count
Voltage
16024
5.0125V
16030
5.0125V
16032
5.0150V
IC200ALG431
8 counts =
2.5mV
5.0175V
5.0150V
16040
5.0125V
16032
5.0100V
16024
16016
GFK-1504N