GE VersaMax IC200PWR001 User Manual page 245

Table of Contents

Advertisement

Module Specifications
Module Characteristics
Points
Module ID
Isolation:
User input to logic (optical)
and to frame ground
Group to group
Point to point
LED indicators
Backplane current
consumption
External power supply:
5 V DC-TTL mode
12/24 V DC mode
Thermal derating
Compatibility
HW,FW vers.
FW release
Output Characteristics
Output voltage:
5 V DC-TTL mode
12/24 V DC mode
Output voltage drop:
5 V DC-TTL mode
12/24 V DC mode
Load current:
5 V DC-TTL mode
12/24 V DC mode
Output leakage current
On response time
Off response time
Protection
GFK-1504N
Chapter 8 Discrete Output Modules
Output Module, 5/12/24 V DC Negative Logic 0.5 A, 32 Points
2 groups of 16 outputs
80808080
250 V AC continuous; 1500 V AC for 1 minute
250 V AC continuous; 1500 V AC for 1 minute
None
One LED per point shows individual point on/off state
FLD PWR LED indicates field power is present
OK LED indicates backplane power is present
5 V output: 140mA maximum
+4.75 to +5.25 V DC, +5 V DC nominal
+10.2 to +30 V DC, +12/24 V DC nominal
Refer to associated diagrams
Cimplicity
Versa
Control
ME
Pro
90
2.11
1.5
2.4
+4.75 to +5.25 V DC, +5 V DC nominal
+10.2 to +30 V DC, +12/24 V DC nominal
0.4V maximum
0.3V maximum
25mA maximum
0.5A at 30 V DC maximum (resistive)
2.0A inrush maximum for 100ms
0.5mA at 30 V DC maximum
0.2ms maximum
1.0ms maximum
No internal fuses
CPU
CPU
CPU
CPU
001
002
005
E05
AA
AA
AA
AA
1.0
1.5
2.1
2.1
8
IC200MDL744
DBI
EBI
GBI
PBI
001
001
001
001
AA
AA
AA
AA
1.1
1.0
1.0
1.0
8-35