GFK-2739
April 2012
*
The VersaMax
IC200BEM003 PROFIBUS Master Module allows a VersaMax
CPU005, CPUE05 or PROFINET Scanner (PNS) to send and receive data on a
PROFIBUS-DP V1 network.
The PROFIBUS Master module provides the following PROFIBUS
communications features:
Supports all standard data rates
Supports a maximum of 3,584 bytes of input data and 3,584 bytes of output
data with a VersaMax CPU; a maximum of 1440 bytes of input data and 1440
bytes of output data with a PNS.
Supports a maximum of 125 PROFIBUS-DP slaves, with a maximum of 244
bytes of input data and 244 bytes of output data for each slave
Supports Sync and Freeze modes
Supports DP-V1 Read, Write and Alarm messages
Has PROFIBUS-compliant module and network status LEDs
This module must be located in a VersaMax Communications Carrier.
The PROFIBUS module receives its firmware upgrades indirectly from the
head end CPU or PNS using the WinLoader software utility. WinLoader is
supplied with any updates to the PROFIBUS module software.
Ordering Information
IC200BEM003
IC200CHS006
Specifications
PROFIBUS support
Power Consumption
I/O Data
With a CPU
With a PNS
PROFIBUS network addresses
Maximum no. of slave devices
Network data rate
Status information
Module isolation
For product standards, general operating specifications, and installation requirements, refer to the VersaMax I/O Modules
Manual, GFK-1504.
*
indicates a trademark of GE Intelligent Platforms, Inc. and/or its affiliates. All other trademarks are the property
of their respective owners.
VersaMax PROFIBUS Master Module
VersaMax Communications Carrier
PROFIBUS-DP V1
450mA at +5V
A maximum of 3584 bytes of input data and 3584 bytes of output data
A maximum of 1440 bytes of input data and 1440 bytes of output data
With either CPU or PNS head end, a maximum of 244 bytes of input data and 244
bytes of output data for each slave.
0 to 125, software-configurable
125
9.6K up to 12 Mbaud (bit/sec)
Slave Status Bit Array Table
Firmware Module Revision
Slave Diagnostic Address
Network to Frame ground: 250VAC continuous, 1500VAC for 1 min
Profibus network to backplane: 1500VAC minimum
VersaMax*
IC200BEM003
PROFIBUS Master Module