GE VersaMax IC200PWR001 User Manual page 37

Table of Contents

Advertisement

2
Connecting the Expansion Cable: RS-485 Differential
For a multiple-rack expansion system, connect the cable from the expansion
port on the Expansion Transmitter to the Expansion Receivers as displayed in
the following figure. If all the Expansion Receivers are the Isolated type
(IC200ERM001), the maximum overall cable length is 750 meters. If the
expansion bus includes any non-isolated Expansion Receivers (IC200ERM002),
the maximum overall cable length is 15 meters.
15M with any
IC200ERM002 ERMs
750M with all
IC200ERM001 ERMs
Install the Terminator Plug (supplied with the Expansion Transmitter module)
into the lower port on the last Expansion Receiver. Spare Terminator Plugs can
be purchased separately as part number IC200ACC201 (Qty 2).
RS-485 Differential Inter-Rack Connection (IC200CBL601, 602, 615)
Expansion
Transmitter or
Expansion
Receiver
Module
Transmitting
Port
26-PIN
FEMALE
Building a Custom Expansion Cable
Custom expansion cables can be built using Connector Kit IC200ACC202,
Crimper AMP 90800-1, and Belden 8138, Manhattan/CDT M2483, Alpha
3498C, or equivalent AWG #28 (0.089mm
2-10
VersaMax Modules, Power Supplies and CarriersUser Manual
ETM
IC200CBL601,
602, 615
Terminator
Plug
PIN
2
FRAME+
3
FRAME-
5
RIRQ/+
6
RIRQ/-
8
RUN+
9
RUN-
12
RERR+
13
RERR-
16
IODT+
17
IODT-
20
RSEL+
21
RSEL-
24
IOCLK+
25
IOCLK-
7
0V
23
0V
1
SHIELD
VARIABLE (SEE
26-PIN
MALE
VersaMax PLC or I/O Station Main Rack (0)
PS
CPU/NIU
VersaMax ExpansionRack 1
PS
ERM
VersaMax ExpansionRack 7
PS
ERM
PIN
2
FRAME+
3
FRAME-
5
RIRQ/+
6
RIRQ/-
8
RUN+
9
RUN-
12
RERR+
13
RERR-
16
IODT+
17
IODT-
20
RSEL+
21
RSEL-
24
IOCLK+
25
IOCLK-
7
0V
23
0V
1
SHIELD
TEXT)
26-PIN
MALE
2
) cable.
Expansion
Receiver
Module
Receiving
Port
26-PIN
FEMALE
GFK-1504N

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents