Wiring for a Compact I/O Carrier (IC200CHS022, IC200CHS025)
Each terminal on a Compact-style I/O Carrier accommodates one solid or
stranded AWG #14 (avg. 2.1mm
cross section) wire, or two wires up to AWG #18 (avg. 0.86mm
Use copper wire rated for 90 degrees C. When inserting two wires in the same
position, the wires must be the same size and type (solid or stranded).
The I/O carrier can accommodate current levels up to 2 Amps per point or 8
Amps per each power and ground, and a voltage range of up to 264 V AC.
Voltage transients up to 300 V AC will not damage the carrier.
For a Box-Style I/O Carrier, recommended terminal torque is 0.37 to 0.45 ft-lbs.
The label provided with the module can be folded and inserted in the label
holder.
Terminal Numbering for a Box- or Spring-Style Compact I/O Carrier
GFK-1504N
Chapter 2 Installation
Field Wiring
Terminals
2
cross section) to AWG #22 (avg. 0.36mm
A17
A18
A13
A14
A15
A16
A7
A8
A10
A11
A12
A9
A1
A2
A3
A4
A5
A6
B17
B18
B13
B14
B15
B16
B7
B8
B9
B10
B11
B12
B1
B2
B3
B4
B5
B6
2
2
2
cross section).
2-21