GE VersaMax IC200PWR001 User Manual page 186

Table of Contents

Advertisement

Module Specifications
Module Characteristics
Points
Module ID
Isolation:
User input to logic
(optical) and to frame
ground
Point to point
LED indicators
Backplane current
consumption
External power supply
Thermal derating
Configuration parameters
Compatibility
HW,FW vers.
FW release
Input Characteristics
Input voltage
User input current
Input impedance
On state voltage
Off state voltage
On state current
Off state current
On response time
Off response time
Configurable filter time
GFK-1504N
Chapter 7 Discrete Input Modules
Input Module, 125 V DC Pos/Neg Logic Isolated 16 Points
16 isolated inputs
80048004
250 V AC continuous; 1500 V AC for 1 minute
250 V AC continuous; 1500 V AC for 1 minute
One LED per point shows individual point ON/OFF status
OK LED indicates backplane power is present
5 V output: 80 mA maximum
None
Refer to associated diagram
Input response times
Cimplicity
VersaPro
Control
ME
90
2.11
1.5
2.4
0 to 150 V DC, 125 V DC nominal
1.7mA typical at 125 V DC, 2.2mA typical at 150 V DC
74 kΩ typical at 125 V DC
90 V DC to 150 V DC
0 V DC to 30 V DC
1.0 mA minimum
0 to 0.1 mA maximum
0.5ms maximum
0 ms, 1.0ms (default), or 7.0ms
CPU
CPU
CPU
CPU
001
002
005
E05
AA
AA
AA
AA
1.0
1.5
2.1
2.1
7
IC200MDL632
DBI
EBI
GBI
PBI
001
001
001
001
AA
AA
AA
AA
1.1
1.0
1.0
1.0
7-33