Module Specifications
Module Characteristics
Points
Module ID
Isolation:
User input to logic
(optical) or frame ground
Group to group
Point to point
LED indicators
Backplane current
consumption
External power supply
Thermal derating
Compatibility
HW,FW vers.
FW release
Output Characteristics
Output voltage
Output voltage drop
Load current
Output leakage current
On response time
Off response time
Protection
Switching frequency
Relay type
Contact type
Contact life
GFK-1504N
Chapter 8 Discrete Output Modules
Output Module, Relay 2.0 A, Isolated Form A 16 Points
16 individually isolated Form A relay outputs
80408040
250 V AC continuous; 1500 V AC for 1 minute
250 V AC continuous; 1500 V AC for 1 minute
250 V AC continuous; 1500 V AC for 1 minute
One LED per point shows individual point ON/OFF state
OK LED indicates backplane power is present
5 V output: 490mA maximum
0 to 125 V DC, 5/24/125 V DC nominal
0 to 265 V AC (47 to 63Hz), 120/240 V AC nominal
None
Cimplicity
Versa
Control
ME
Pro
90
2.11
1.0
2.2
0 to 125 V DC, 5/24/125 V DC nominal
0 to 265 V AC (47 to 63Hz), 120/240 V AC nominal
0.3V maximum
10mA per point minimum
2.0A for 5 to 265 V AC maximum (resistive)
2.0A for 5 to 30 V DC maximum (resistive)
0.2A for 31 to 125 V DC maximum (resistive)
Not applicable (open contact)
10ms maximum
10ms maximum
No internal fuses or snubbers
20 cycles per minute (inductive load)
Fixed coil, moving armature
Silver alloy
See appendix D
CPU
CPU
CPU
CPU
001
002
005
E05
AA
AA
AA
AA
1.0
1.5
2.1
2.1
8
IC200MDL940
DBI
EBI
GBI
PBI
001
001
001
001
AA
AA
AA
AA
1.1
1.0
1.0
1.0