9
IC200MDD850
Mixed Module, Output Relay 2.0 A per Pt Isolated 8 Points /
Input 240 V AC Isolated 4 Points
Backplane Power Drain per Point
The module's backplane 5 V power requirement increases as the number of
output points that are simultaneously on increases. The following chart displays
the relationship between the number of points on and the maximum current
required.
mA = 56 + (28 x number of output points on)
9-50
VersaMax Modules, Power Supplies and Carriers User's Manual
Maximum Current Drawn from Backplane (mA)
275
168
56
0
4
Number of Output Points On