Jumper Selection
Jumpers on the carrier can be used to select the output range and output
default mode.
Range Jumper
If no jumper is installed on pins B1 and B2, outputs are configured for the
bipolar range of –10V to +10V. With a jumper installed, the outputs are
configured for the unipolar range of 0V to +10V.
Hold Jumper
If no jumper is installed on pins B2 and B3, outputs hold their last state (the last
commanded value from the backplane) if backplane power or communications
are interrupted or the PLC is stopped. With a jumper installed, outputs default
to 0V. This should only be changed with the field power and backplane power
removed.
Wiring Example
GFK-1504N
Chapter 11 Analog Output Modules
Analog Output Module, 13 Bit Voltage 12 Channels
Range Jumper (JMP 1)
None
Installed
Hold Jumper (JMP 2)
None
Installed
Jumper installed = unipolar range
no jumper = bipolar range
Jumper installed = default to 0V
no jumper = hold last state
Load 1
Load 2
-
+
IC200ALG327
Range
-10V to +10V
0V to +10V
Output Default
Hold Last State
0V
JMP 1
RET
JMP 2
Shield
V OUT 1
Return 1, 2
V OUT 2
Shield
Field Return
Field Power
11
11-37