GE VersaMax IC200PWR001 User Manual page 101

Table of Contents

Advertisement

Din Rail Mounting
The I/O carrier snaps easily onto a 7.5 mm x 35 mm DIN rail. The DIN rail must
be electrically grounded to provide EMC protection. The rail must have a
conductive (unpainted) corrosion-resistant finish.
For applications requiring maximum resistance to mechanical vibration and
shock, the carrier must also be panel-mounted. Refer to chapter 2 for
installation instructions.
Features
The Compact Box-Style I/O carrier supports wiring for up to 32 I/O points
and 4 common/power connections.
Easily-set keying dials to assure installation of the correct type of module
on the carrier. Keys are set to match the keying on the bottom of the
module. Refer to Appendix D for a complete list of module keying
assignments.
Carrier-to-carrier mating connectors for quick installation of the backplane
connection with no additional cables or tools needed.
Module latch hole for securely fastening the module to the carrier.
A printed wiring card provided with each I/O module can be folded and
inserted in the built-in card holder.
GFK-1504N
Chapter 4 Carriers
Carrier to Carrier
Connector
Module to Carrier
Connectors
Keying Dials
Field Wiring
Terminals
IC200CHS022
Compact Box-Style I/O Carrier
Module
latch hole
Holder for
wiring card