GE VersaMax IC200PWR001 User Manual page 113

Table of Contents

Advertisement

5
IC200CHS011
Barrier-Style Interposing I/O Terminals
The carrier accommodates current levels up to 2 A per point or 8 A per each
power and ground, and a voltage range of up to 264 V AC. Voltage transients
up to 300 V AC will not damage the carrier.
One or more Auxiliary I/O Terminal Strips can be added to provide extra field
wiring connections if needed. Auxiliary I/O Terminal Strips insert directly into
the lower edge of the I/O Carrier.
Din Rail Mounting
The Interposing I/O Terminals unit can be mounted on the same DIN rail as the
Connector-Style I/O Carrier, or on a separate DIN rail as illustrated in the
following figure. For applications requiring maximum resistance to mechanical
vibration and shock, the Interposing I/O Terminals must also be panel-mounted.
Refer to chapter 2 for installation instructions.
GFK-1504N
Chapter 5 Interposing Terminals and Auxiliary I/O Terminal Strips
5-3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents