GE VersaMax IC200PWR001 User Manual page 126

Table of Contents

Advertisement

5
IC200CHS111, Main Base
IC200CHS112, Expansion Base
Relay-Style Interposing I/O Terminals
Field Wiring
Power for operation of the relay coils must be provided by an external 24V DC
power supply. This power must be provided to both the main base and the
expansion base. Connection of this external power supply is made at the
terminals A17 & A18 (B17 & B18 for the expansion base). This power
connection is for the relay coils only. User loads must be powered by an
external source.
Each relay, status LED and fuse is labeled to indicate the specific point on the
VersaMax output module they are associated with. Components labeled A1-
A16 correspond to points Q1-Q16. Components labeled B1-B16 correspond to
points Q17-Q32. Each point is associated with 3 terminal connections, labeled
NO (Normally Open), C (Common), and NC (Normally Closed). User loads may
be connected between C and NO, C and NC, or both.
5-16
VersaMax Modules, Power Supplies and Carriers User's Manual
J2
A16
A15
A14
A13
A12
A11
A10
A16
A15
A14
A13
A12
A11
A10
24VDC
+
A18
J1
A9
A8
A7
A6
A5
A4
A3
A9
A8
A7
A6
A5
A4
A3
-
A17
A2
A1
A2
A1
A1
NO C NC
V
Q1
GFK-1504N

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents