8
IC200MDL750
Output Module, 12/24 V DC Positive Logic 0.5 A, 32 Points
Discrete output module IC200MDL750 provides two groups of 16 discrete
outputs. The outputs are positive or sourcing type outputs. They switch the
loads to the positive side of the DC supply and thus supply current to the loads.
Q
Note: 12 V output functionality requires module version IC200MDL750B or
higher.
An external DC power supply must be provided to switch power to the loads.
Intelligent processing for this module is performed by the CPU or NIU. The
module receives 32 bits of discrete output data.
LED Indicators
Individual green LEDs indicate the on/off state of the output points. Operation of
these LEDs is dependent on field power but independent of load conditions.
The green FLD PWR LED is ON when field power is applied to the module.
The green OK LED is ON when backplane power is present to the module.
8-38
VersaMax Modules, Power Supplies and Carriers User's Manual
Q
1
2
3
4
5
6
7
8
9
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
FLD
PWR
10 11 12 13 14 15 16
IC200MDL750
OUTPUT
POS GRP
1234567
FLD
OK
PWR
OK
12/24VDC
.5A
32PT
831
GFK-1504N