IC200ALG327
Analog Output Module, 13 Bit Voltage 12 Channels
Scaling for Bipolar Outputs
The following graph illustrates the relationship between the output voltage
measured at the field terminals and the data that is output by the module, when
outputs are set up for the bipolar range.
Count vs Output Voltage, Bipolar
Voltage
12
10
8
6
4
2
0
-2
4
-6
-8
-10
-12
-32000 -25600 --19200 12800 -6400 0
Voltage can be calculated using the following equation:
Vout = ( (analog counts x 20.48) / 65536 )
The count value must be a multiple of 4. If the module receives a count value
that is not a multiple of 4, it rounds the value down to the closest multiple of 4.
For example:
11-40
VersaMax Modules, Power Supplies and Carriers User's Manual
6400 12800 19200 25600 32000
Count
Count
Voltage
16024
5.0075V
16026
5.0075V
16028
5.00875V
4 counts
= 1.25mV
5.0100V
5.00875V
16032
5.0075V
16028
5.00625V
16024
16020