GE VersaMax IC200PWR001 User Manual page 93

Table of Contents

Advertisement

4
IC200CHS002
Box-Style I/O Carrier
Field Wiring Terminals
2
Each terminal accommodates one solid or stranded AWG #14 (avg. 2.1 mm
2
cross section) to AWG #22 (avg. 0.36 mm
cross section) wire, or two wires up
2
to AWG #18 (avg. 0.86 mm
cross section).
A1
A2
A3
A5
A6
A7
A8
A9
A11 A12
A13
A15 A16
A17
A18
A4
A14
A10
B2
B3
B4
B5
B6
B7
B8
B9
B11 B12
B13
B14
B15 B16
B17
B18
B1
B10
The carrier accommodates current levels up to 2 A per point or 8 A per each
power and ground, and a voltage range of up to 264 V AC. Voltage transients
up to 300 V AC will not damage the carrier.
One or more Auxiliary I/O Terminal Strips can be added to provide extra field
wiring connections if needed. Auxiliary I/O Terminal Strips insert directly into
the lower edge of the I/O Carrier.