GE VersaMax IC200PWR001 User Manual page 204

Table of Contents

Advertisement

Module Specifications
Module Characteristics
Points
Module ID
Isolation:
User input to logic (optical)
and to frame ground
Group to group
Point to point
LED indicators
Backplane current consumption 5 V output: 140 mA maximum
External power supply
Thermal derating
Configuration parameters
Compatibility
HW,FW vers.
FW release
Input Characteristics
Input voltage
User input current
Input impedance
On state voltage
Off state voltage
On state current
Off state current
On response time
Off response time
Configurable filter time
GFK-1504N
Chapter 7 Discrete Input Modules
Input Module, 5/12 V DC Pos/Neg Logic Grouped 32 Point
32 (4 groups of 8)
80088008
250 V AC continuous; 1500 V AC for 1 minute
250 V AC continuous; 1500 V AC for 1 minute
None
One LED per point shows individual point ON/OFF
status
OK LED indicates backplane power is present
None
No derating
Input response times
Cimplicity
VersaPro
Control
ME
90
2.11
1.5
2.4
0 to +15 V DC, +5/12 V DC nominal
1.8 mA typical at 5 V DC, 4.9 mA typical at 12 V DC
2.4KΩ typical at 12 V DC
+4.2 to +15 V DC
0 to +2.6 V DC
1.45 mA minimum
0 to 0.7 mA maximum
0.25ms maximum
0 ms, 1.0ms (default), or 7.0ms
CPU
CPU
CPU
CPU
001
002
005
E05
AA
AA
AA
AA
1.0
1.5
2.1
2.1
7
IC200MDL644
DBI
EBI
GBI
PBI
001
001
001
001
AA
AA
AA
AA
1.1
1.0
1.0
1.0
7-51