GE VersaMax IC200PWR001 User Manual page 465

Table of Contents

Advertisement

Mixed Module, 24 V DC Positive Logic Input 20 Points / Output 12 Point /
(4) High-speed Counter, PWM, or Pulse Train Configurable Points
Command
Command
Word (hex)
0208
Load Home
Value
0n0B
Load ON Preset
0n15
Load OFF
0n1F
Load Preload
0n3B
Load Stop
Mode (or
Resume
Decelerate
GFK-1504N
Chapter 13 Mixed Discrete/High-Speed Counter Module
Changes the home value for the Type B2 counter.
Sets up the output turn on points within the counter range. There is one
output associated with each counter.
Example: To set counter 1 output to turn on at 5000 (1388H) counts,
load:
Command Code: 010B
LS data word: 1388
Sets up the output turn off points within the counter range. There is one
Preset
output associated with each counter.
Example: To set counter 1 output to turn off at 12000 (2EE0H) counts,
load:
Command Code: 0115
LS data word: 2EE0
Changes the count value loaded into the counter Accumulator when
the Preload input is activated.
Example: To make counter 1 start at 2500 (09C4H) counts at its
preload signal, load:
Command word: 011F
LS data word: 09C4
Changes a Pulse Train output's deceleration to stop the Ramp
immediately when the Output Enable bit goes Off. The Ramp function
must be enabled.
Example: to set up a Pulse Train output for Stop Ramp (0002)
Mode)
operation on ch.1:
Command word: 013B
LS data word: 0002
The same command can be used to reset the output to Decelerate
mode (the default) by entering the value 0001 in the LS data word.
Example: reset the same Pulse Train output to Decelerate (0001)
operation:
Command word: 013B
LS data word: 0001
IC200MDD841
Description
13
13-25