GE VersaMax IC200PWR001 User Manual page 329

Table of Contents

Advertisement

10
IC200ALG240
Analog Input Module, 16 Bit Voltage/Current, 1500 V AC Isolation, 8 Channels
Configurable Parameters
The default parameters of this module can be used in many applications. The
module can be software-configured when it is installed in a VersaMax PLC
system, or an I/O Station controlled by a Network Interface Unit that is version
2.0 or above.
Module
Description
Parameter
Analog Input
Starting offset for the module's analog input data.
Data
Reference
Analog Input
Word length of the module's analog input data.
Data Length
Line
Specifies the line filter frequency.
Frequency
Report Faults Enables or disables Fault Reporting for the entire
Module.
%AI Default
Specifies whether the module will go to the specified
/Hold Last State
channel defaults (see below) or hold their last states if
power or communications are lost.
Current
Specifies whether the channel will be a voltage or
/Voltage
current input. If the Channel type is Current, the range
is 4 to 20mA. If Channel type is Voltage, the range is
–10 to +10V.
Channel
Specifies if the channel should input data received
Active
from the CPU or NIU. If a channel is "inactive" space
is still allocated for it.
Span Low
Actual current (in microAmps) or voltage (in milliVolts)
to be scaled from low engineering units value.
Span High
Actual current in microAmps or voltage in millivolts to
be scaled from the high engineering units value.
Engineering
The engineering units value that is considered
Low
equivalent to the low span (actual) value.
Engineering
The engineering units value that is considered
High
equivalent to the high span (actual) value.
Alarm Low
The low alarm limit for the channel, in engineering
units.
Alarm High
The high alarm limit for the channel, in engineering
units.
Default
The value to be input when the module is in a default
condition.
10-14
VersaMax Modules, Power Supplies and Carriers User's Manual
Default
Choices
User selectable
8
0–8
60 Hz
50 Hz, 60 Hz
Enabled
Enabled,
Disabled
Default
Default /Hold
I (Current)
I (Current),
V (Voltage)
Active
Inactive (off),
Active (on)
4,000 µA
0 to 25,000 µA
–10,000 to
+10,000mV
20,000 µA
0 to 25,000 µA
–10,000 to
+10,000mV
0 to 25,000 µA
4000
–10,000 to
+10,000mV
0 to 25,000 µA
20000
–10,000 to
+10,000mV
4000
-32768 to +32767
20000
-32768 to +32767
0
-32768 to +32767
GFK-1504N

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents