Backplane Power Drain per Point
The module's backplane 5 V power requirement increases as the number of
points that are simultaneously on increases. The following chart displays the
relationship between the number of points on and the maximum current required.
mA = 40 + (28 x number of output points on)
GFK-1504N
Chapter 9 Discrete Mixed Modules
Mixed Module, 24 V DC Positive Logic Input 20 Points /
Maximum Current Drawn from Backplane (mA)
375
208
40
0
6
Number of Output Points On
IC200MDD840
Output Relay 2.0 A 12 Points
12