GE VersaMax IC200PWR001 User Manual page 445

Table of Contents

Advertisement

Mixed Module, 24 V DC Positive Logic Input 20 Points / Output 12 Point /
(4) High-speed Counter, PWM, or Pulse Train Configurable Points
Module Specifications
Module Characteristics
Points
Module ID
Isolation:
User I/O to logic (optical) and frame
ground
Point to point
Group to group
Indicators
Backplane current consumption
External power supply
Thermal derating
Compatibility
HW, FW vers.
FW release
High-speed Channels
Input frequency (Type A Counter
PWM Output frequency
Pulse Output frequency
Counter Output latency
Input Characteristics
Input voltage
On state voltage
Off state voltage
On state current
Off state current
On/off response time
Count Input Impedance
Count User input current
Standard Input Impedance
Standard User input current
Output Characteristics
Inrush current
Continuous Load Current
Output voltage drop
On/off response time
Protection
Diagnostics
GFK-1504N
Chapter 13 Mixed Discrete/High-Speed Counter Module
20 DC inputs & 12 DC outputs
FFFF9801
250VAC continuous, 1500VAC for 1 minute
250VAC continuous, 1500VAC for 1 minute
One LED per point shows individual point on/off state
FLD PWR indicates field power is present
OK LED indicates backplane power is present.
3.3V output: 130mA, 5V output: 30mA
+24 V DC nominal, +18 to +30 V DC
See diagrams
PME programming
CPU
CPU
software
001
BB
All
1.1
80KHz maximum
2 KHz maximum
5 KHz maximum
0.5mS max. between output point updates
+24 V DC nominal, 0 to +30 V DC
+15.0 to +30.0 V DC
0 to +5.0 V DC
3.0 to 8.0mA
0 to 0.5mA
7.0ms max. (6.25µs max. for count inputs and 100µs for
Preload/Strobe inputs)
6.6 kΩ maximum
5.5mA at +24 V DC
9.6 kΩ maximum
4.0mA at +24 V DC
2.0A maximum for 100ms
0.5A maximum
0.3V maximum
500µs, maximum
no internal fuses
13 words of status data
CPU
CPU
DBI
002
005
E05
001
AA
AA
AA
AA
1.5
2.1
2.1
1.1
13
IC200MDD841
EBI
GBI
PBI
001
001
001
AA
AB
BB
1.0
1.1
1.1
13-5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents