IC200ALG321
Analog Output Module, 12 Bit Voltage 0 to 10 V DC 4 Channels
Jumper Selection
A jumper on the carrier can be used to select the output default mode.
If no jumper is installed on pins B13 and B14 outputs hold their last state (the
last commanded value from the backplane) if backplane power or
communications are interrupted or the PLC is stopped. With a jumper installed,
if such conditions occur outputs default to 0 volts. This should only be changed
with field power and backplane power removed.
Wiring Example
Jumper present
selects default to 0
24VDC
11-12
VersaMax Modules, Power Supplies and Carriers User's Manual
Jumper
Selects
None
Hold Last State
JMP 1
Default to 0
Load
Load
-
+
VOUT 1
RET 1
Shield
VOUT 4
RET 4
Shield
JMP 1A
JMP 1B
Field Return
Field Power