ABB i-bus
KNX
Commissioning
Note
The additional functions Slave and Staircase lighting can adopt three operating states:
Additional function is not active: The additional function has been deactivated via a
telegram with value 0 received on the function's Enable additional function group object. In this
state, the group/ballast behaves normally. Accordingly, the group or ballast settings apply.
In this state, an ON telegram does not start the additional function. The additional function can
only be started after a telegram with the value 1 has been received on the Enable additional
function group object.
Additional function is in standby: The additional function is active but has been interrupted,
e.g. by an OFF telegram. The group/ballast is in standby. An ON telegram (telegram on the
Switch group object) retriggers the additional function, i.e. the staircase lighting runs and the
slave starts responding to the Brightness value of slave group object or internally to its master
group or ballast again.
Additional function running: Staircase lighting runs; the Slave function receives brightness
values from the master. With corresponding parametrization of the switching telegrams, the
additional functions can be set to standby mode.
State on download and KNX recovery: This can be programmed in the Slave or Staircase
lighting parameter window for the group/ballast.
When the corresponding group object for the status message of the additional function is
enabled via the settings, the status of the additional function (activated/deactivated) is sent via
the respective Activate additional function/Status group object.
Parameter settings
Options:
Individual
Apply from template
This parameter defines whether the group/ballast settings are taken from the template or
individually set.
Individual: The group/ballast is individually parametrized. Corresponding parameters for the
group/ballast are shown. The content of the individual parameters is the same as that in the
template parameters.
Apply from template: The group/ballast takes its parameters from the template.
DG/S x.64.1.1 | 2CDC507164D0201 137