ABB i-bus
KNX
Commissioning
3.3.5

Lighting converter x group objects

As soon as an emergency lighting test is enabled in the X lighting converter parameter window, the Trigger
em lighting test group object for converter x is enabled. The following emergency lighting tests can be
triggered for the emergency lighting converter via this group object:
Function test
Partial duration test
Duration test
Battery query
The tests are described in 1.2.1, Emergency lighting tests, p. 8.
No.
928, 931... Trigger em lighting test (CTC)
This group object is enabled if an Emergency light x is enabled in X lighting converter/Emergency light template parameter
window, p. 155. The object can adopt one of 3 data formats. The data format is defined in the A lighting converter, Emergency
light x parameter window by setting the Enable Group Objects "Trigger em lighting test" parameter to Yes, KNX format
DPT_CTC.
This group object triggers an emergency lighting test for emergency light x. It does not send the status or the emergency
lighting test result from the gateway on the KNX.
The following numbering applies to the list below:
2
The bit number is identical to the exponent of the bit, e.g. number 2 corresponds to 2
The value of the byte contains the information on which emergency lighting test to trigger or which action to execute:
Value 0
Value 1
Value 2
Value 3
Value 4
Value 5
Value 6
Value 7...255
If a new test is requested on the group object before the ongoing test has ended, this is immediately interrupted and the new
test is requested. This is also the case when the ongoing test is requested again. Only one test can be undertaken on the
emergency lighting converter at any time.
208 2CDC507164D0201 | DG/S x.64.1.1
Function
7
6
5
4
3
2
2
2
2
2
2
= Reserved, no function
= Function test requested (corresponds to DALI Cmd 227)
= Duration test requested (corresponds to DALI Cmd 228)
= Partial duration test requested
= Stops the test currently running (corresponds to DALI Cmd 229)
= Function test flag reset (corresponds to DALI Cmd 230). This means that if a function test is requested
and not executed, a flag is set in the emergency lighting converter indicating that the test is pending.
This flag can be canceled so that a function test is no longer pending.
= Duration test flag reset (corresponds to DALI Cmd 231). This means that if a duration test is requested
and not executed, a flag is set in the emergency lighting converter indicating that the test is pending.
This flag can be canceled so that a duration test is no longer pending.
= Reserved, no function
Note
The result of the emergency lighting test for each converter can be sent on the KNX with the addressed group object
Em lighting test result (no. 42) or the Em lighting test status group object (no. 929ff).
Group object name
Output A - Emergency light x
1
0
2
2
Data type
Flags
1 byte
C, W
DPT_CTC
2
.