ABB i-bus
KNX
Commissioning
Note
The Turn off brightness function can be applied to the whole DALI output, all ballasts and all groups.
It must first be enabled in the X Output x functions parameter window along with Activate fct Turn off
brightness group object.
To define whether a ballast or a group reacts to the output's Turn off brightness function, make the
settings in the relevant Ballast x or Group x parameter window.
With active additional function.
Reaction on...
...Brightness value
Options:
When the Staircase lighting function is activated, this parameter defines the reaction to a Brightness value
telegram on the Brightness value group object.
No reaction: A Brightness value telegram is ignored.
Function switches to standby: A Brightness value telegram ends the Staircase lighting function; the
group executes the telegram via the Brightness value group object. The Staircase lighting function
switches to standby and waits for reactivation via the Activate fct Staircase lighting group object or via
an ON telegram on the Switch group object.
...Relative dimming
Options:
When the Staircase lighting function is activated, this parameter determines the reaction to a Dim telegram
on the Relative dimming group object.
No reaction: A Dim telegram is ignored.
Function switches to standby: A Dim telegram ends the Staircase lighting function; the group executes
the telegram. The Staircase lighting function switches to standby and waits for reactivation via the
Activate fct Staircase lighting group object via an ON telegram on the Switch group object.
130 2CDC507164D0201 | DG/S x.64.1.1
No reaction
Function switches to standby
No reaction
Function switches to standby