ABB i-bus KNX Product Manual page 90

Dali-gateway basic dg/s x.64.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
Note
Flexible dimming time is received via the Output x Flexible time for dimming/fade time group object and
affects various output functions:
To use the Flexible dimming time function you first need to enable the output's Flexible time for
dimming/fade time group object in the A Output/Functions parameter window. You also need to select
the function for the parameter that can be changed via KNX. We recommend that you only change one
time via KNX. Otherwise the dimming time has to be rewritten on the ballast every time a function is
called, which impairs function performance.
88 2CDC507164D0201 | DG/S x.64.1.1
Dimming time for turn on/off value
Dimming time for brightness value
Dimming time for slave brightness value
Scene transition time
Selection of Fixed fade time option:
Dependent parameters:
Dimming time (0 = jump to)
Options:
0...2...65,535 s
This parameter defines how long it takes to dim up to the set brightness value. This time only
relates to the output's Brightness value telegram (8-bit).
0 s: Jump to. The output immediately switches to the brightness value.
1...65,535 s: During this time, the output is dimmed up to the brightness value.

Advertisement

Table of Contents
loading

Table of Contents