ABB i-bus KNX Product Manual page 198

Dali-gateway basic dg/s x.64.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
No.
41
This group object is enabled if the Em lighting test status (addr) parameter is set to Yes in the X lighting converter parameter
window, p. 149.
This group object consists of two bytes.
The High byte contains the emergency lighting converter test state given in the Low byte, but in coded form. Automatic status
feedback is only sent for the set DALI emergency lighting converters. The emergency lighting test itself is requested for each
converter via the addressed group object Trigger em lighting test (no. 40) or the Trigger em lighting test/Status group object
(no. 928ff).
The following numbering applies to the list below:
High byte
15
2
The bit number is identical to the exponent of the bit, e.g. number 2 corresponds to 2
Bit 0...5
Bit 6
Bit 7
Bit 8 ... 10
Bit 11 and 12
Bit 13
Bit 14
Bit 15
Bit 14 and 15 only relate to an emergency lighting converter. If the device is a normal DALI device, bit 6 and 7 are not
evaluated.
196 2CDC507164D0201 | DG/S x.64.1.1
Function
Em lighting test status (addr)
Dependent on parameter
14
13
12
11
10
9
2
2
2
2
2
2
= Contains the binary number (0...63). This number is the number of the DALI device that the High byte
information relates to, plus 1.
= 0, without function or not taken into account in the request evaluation.
= 1, status value request. If a telegram with a set bit 7 is received, it is interpreted as a test state status
request and corresponding feedback is sent. When the answer is returned, the value of bit 7 is reset to
0.
= 000, no test
= 001, function test
= 010, partial duration test
= 011, duration test
= 100, battery query (does not require a time and therefore is not displayed)
= 101 and 110 without function not taken into account in evaluation
= 111, there is no valid test state or the queried DALI device does not support DALI Standard
IEC 62386-202 for emergency lighting converters. The content of bit 8...15 is invalid.
= 00, test finished (the Em lighting test result group object shows whether the test is a pass or fail)
= 01, test pending, not yet started
= 10, test running
= 11, test interrupted
= 1, testing manually started
= 1, lamp fault (emergency lighting converter)
= 1, device (emergency lighting converter) fault
Group object name
Output A
Em lighting test status (addr)
Low byte
8
7
6
5
4
2
2
2
2
2
2
Data type
2 byte
non DPT (ACTS)
3
2
1
0
2
2
2
2
.
Flags
C, R, W, T