Output: Functions (Turn Off Brightness/Burn-In/Slave Offset/Partial Failure) Parameter Window; X Output: Functions (Turn Off Brightness/Burn-In/Slave Offset/Partial Failure Parameter Window - ABB i-bus KNX Product Manual

Dali-gateway basic dg/s x.64.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
3.2.3.3
X Output: Functions
(Turn off brightness/Burn-in/Slave offset/Partial failure) parameter window
Settings for output X (A and/or B) functions are made in this window.
The functions have a priority order:
For instance, this means that if a ballast or the group is in burn-in mode, a forced operation is mapped
from 50% to 100%.
If either the Forced operation/Block or Partial failure function is activated, the gateway only executes
incoming KNX commands in the background. The system reacts as follows in this case:
Switching, brightness value and scene commands are invisibly updated in the background, memorizing the
end brightness values immediately without transition times. Dimming commands are ignored.
Once the higher-level function ends, the ballast or group adopts the brightness value that would have
occurred if the higher-level function had not been executed. This also applies to the operating state for the
Slave and Staircase lighting functions. As long as a Staircase lighting function is activated it remains in
standby. If Slave mode is active, it responds to its master again as soon as the higher-level function ends.
Forced operation/Block function
Partial failure function
Manual operation
Slave/Staircase lighting, Scenes function and normal KNX commands
DG/S x.64.1.1 | 2CDC507164D0201 67