ABB i-bus
KNX
Commissioning
No.
33
This group object is enabled if the Enable DALI scenes parameter is set to Yes in the X DALI configuration parameter window,
p. 35.
This 8-bit group object sends a Scene telegram using a coded telegram which integrates the groups in a KNX scene. The
telegram contains the number of the scene concerned as well as the information as to whether to recall it or assign the current
brightness values in the scene to the groups in the scene.
Telegram value (1 byte):
Other numeric values do not affect the Scenes 1...16 group objects.
For further information see: Code table 8-bit scene, p. 227
34
This group object is enabled if the Enable Group object "Burn-in lamps/Status" parameter is set to Yes in the X Output:
Functions (Turn off brightness/Burn-in/Slave offset/Partial failure) parameter window, p. 67.
This group object activates or deactivates the Burn-in function. It also indicates burn-in status. If at least one ballast is
executing the Burn-in function, the value of the object is 1.
After receiving a telegram with the value 1, all ballasts intended for burn-in can only be controlled at 0% (OFF) or 100%
brightness. Whether or not a ballast or group is taken into account during burn-in is defined in the A groups or A ballasts
parameter window using the Enable Lamp burn-in function object "Burn-in lamps" group object. Incoming telegrams affect all
ballasts and groups on the DALI output intended for burn-in.
Burn-in time is set individually for each ballast or group. After it has elapsed, the group/ballast can be dimmed as usual, and
the programmed light scene can be recalled.
If another telegram with the value 1 is received on the Burn-in lamps group object during the burn-in time, the time restarts
from the beginning.
A telegram with the value 0 deactivates the Burn-in function and enables "normal" operation.
The burn-in time is only counted if a ballast is connected to output A and has a supply voltage. The burn-in time counts in five
minute steps.
Telegram value:
The DALI values are invisibly updated in the background and set after the burn-in process.
192 2CDC507164D0201 | DG/S x.64.1.1
Function
8-bit scene
Dependent on parameter
M0SS SSSS
(MSB) (LSB)
M: 0 = Scene is recalled
1 = Scene is stored (if allowed)
S: Scene number (1... 13: 00000000...00001101)
KNX 8-bit telegram value
Decimal
00
01
02
...
128
129
130
...
Burn-in lamps/Status
Dependent on parameter
1 = Activate function
0 = Deactivate function
Note
Individual groups or ballasts can also be burned in via the Burn-in lamp/Status group object for the group/ballast.
Group object name
Scene 1...16
Enable DALI scenes
Meaning
Hexadecimal
00h
Recall scene 1
01h
Recall scene 2
02h
Recall scene 3
...
...
80h
Store scene 1
81h
Store scene 2
82h
Store scene 3
...
...
Output A
Enable Group object "Burn-in lamps/Status"
Data type
Flags
1 byte
C, W
DPT 18.001
1 bit
C, R, W, T
DPT 1.010