Commissioning
Enable Group object
"Burn-in lamps/Status"
Options:
Linked group object:
This parameter enables a group object which triggers burn-in for the whole output. However, burn-in must
first be enabled in the ballast and group in the Functions parameter window. This group object also detects
the burn-in status of the output provided at least one ballast is in burn-in mode, as this sets the status.
Yes: The group object is enabled. The group object is evaluated in the output, group or ballast in order
to trigger burn-in.
No: The group object is not enabled.
Whether a ballast or group evaluates this group object is defined for each ballast/group in the
corresponding Ballast x or Group x parameter window.
Note
However, burn-in can also be triggered for individual ballasts or groups via a corresponding Burn-in
lamps group object or via the i-bus
Note
Continuous dimming of lamps which are not burnt in can prevent the lamp from reaching its maximum
defined brightness, making the required brightness value in the area unachievable.
To guarantee maximum lamp life and correct lamp function in the dimmed state, vapor filled lamps must
be operated for a certain number of hours at 100% brightness during initial operation before they can be
permanently dimmed.
For details, please see the technical data for the lamps.