Commissioning
Whether a ballast or group evaluates this group object is defined for each ballast/group in the
corresponding Ballast x or Group x parameter window.
76 2CDC507164D0201 | DG/S x.64.1.1
Forward partial failure information
The Partial failure function allows lighting to be controlled regardless of a failed component.
The information can be forwarded internally or via an external group object.
Internal to DALI output
Options:
Yes
No
Yes: The information from the Partial failure function is forwarded internally on the DALI
output. No group object is required.
No: The information from the Partial failure function is not forwarded internally on the
DALI output.
Externally via object
"Activate partial failure/Status"
Options:
Yes
No
Linked group object:
Yes: The group object is enabled. It sends information on the KNX indicating that a
partial lighting failure has been detected. The status of the partial failure is also
indicated.
No: The information from the Partial failure function is not forwarded on the KNX.
Activate partial failure/Status