ABB i-bus KNX Product Manual page 77

Dali-gateway basic dg/s x.64.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
Active em lighting event
reported by em lighting converter
Options:
Yes
No
Yes: An emergency lighting event will trigger the reaction to partial failure. The number of
emergency lighting events is defined by the next parameter.
No: An emergency lighting event is not counted as a partial failure.
Selection of Yes option:
Dependent parameters:
No. of detected em lighting events
must be greater than or equal to
Options:
1...64
If the number of emergency lighting events reaches the number defined here, this meets a
criterion for partial failure and the set actions are executed.
Lamp/ballast fault
Options:
Yes
No
Yes: A lamp or ballast fault will trigger the reaction to partial failure. The number of faults is
defined by the next parameter. Note: the DALI output must be monitored in order to detect a
ballast fault.
No: A lamp or ballast fault is not counted as a partial failure.
Selection of Yes option:
Dependent parameters:
No. of detect. lamp/ballast faults
must be greater than or equal to
Options:
1...64
If the number of lamp/ballast faults reaches the number defined here, this meets a criterion
for partial failure and the set actions are executed.
DG/S x.64.1.1 | 2CDC507164D0201 75