ABB i-bus KNX Product Manual page 121

Dali-gateway basic dg/s x.64.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
...Brightness value
Options:
When the Slave function is activated, this parameter defines the reaction to a Brightness value telegram
on the Brightness value group object.
No reaction: A Brightness value telegram is ignored.
Function switches to standby: A Brightness value telegram ends the Slave function; the group
executes the telegram via the Brightness value group object. The Slave function switches to standby
and waits for reactivation via the Activate fct Slave group object or via an ON telegram on the Switch
group object.
...Relative dimming
Options:
When the Slave function is activated, this parameter can be used to define the reaction to dimming
telegram to the group object Relative dimming.
No reaction: A Dim telegram is ignored.
Function switches to standby: A Dim telegram ends the Slave function; the group executes the
telegram. The Slave function switches to standby and waits for reactivation via the Activate fct Slave
group object or via an ON telegram on the Switch group object.
...Recall scene
Options:
When the Slave function is activated, this parameter defines the reaction to a scene recall.
No reaction: A scene recall is ignored.
Function switches to standby: A scene recall ends the Slave function; the group executes the recall.
The Slave function switches to standby and waits for reactivation via the Activate fct Slave group
object or via an ON telegram on the Switch group object.
No reaction
Function switches to standby
No reaction
Function switches to standby
No reaction
Function switches to standby
DG/S x.64.1.1 | 2CDC507164D0201 119