ABB i-bus KNX Product Manual page 214

Dali-gateway basic dg/s x.64.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
No.
930, 933... Emergency lighting converter status
This group object is enabled if there is an Emergency light x enabled in the X lighting converter/Emergency light template
parameter window, p.155 and the Enable Group objects "Emergency lighting converter status" parameter is set to Yes in the
A lighting converter, Emergency light x parameter window.
This group object transmits the status of the emergency lighting converter on the KNX.
The information is transmitted in a 2-byte group object with the following coding:
The coding is based on numeric values generated from bit fields of various lengths:
CM provides the status of various emergency lighting converter operating states
voltage failure)
10 - 15 = Reserved, no function
HS Emergency lighting converter hardware status (bit coded)
Bit 2 - 3 = Reserved, no function, has value 0
FP Status indicating whether a function test is pending (2-bit numeric value 0...3)
DP Status indicating whether a duration test is pending (2-bit numeric value 0...3)
PP Status indicating whether a partial duration test is pending (2-bit numeric value 0...3)
CF general fault status (2-bit numeric value 0...3)
212 2CDC507164D0201 | DG/S x.64.1.1
Function
0 = No information available
1 = Normal mode is active, all OK (emergency lighting converter switches to emergency operation if there is a mains
2 = Inhibit mode active
3 = Inhibit mode activated by hardware
4 = Rest mode active
5 = Emergency mode active
6 = extended emergency lighting mode active
(Emergency lighting converter is in Prolong Time. Run-on phase when emergency mode ends.)
7 = Function test running
8 = Duration test running
9 = Partial duration test running
Bit 0 = 1 Inhibit mode active via hardware
0 Inhibit mode not active via hardware
Bit 1 = 1 Hardware switch is on (emergency light activated via hardware input)
0 Hardware switch is off
0 = State unknown
1 = No function test pending
2 = Function test pending
3 = Reserved, no function
0 = State unknown
1 = No duration test pending
2 = Duration test pending
3 = Reserved, no function
0 = State unknown
1 = No partial duration test pending
2 = Partial duration test pending
3 = Reserved, no function
(fault status according to DALI Command 252 – elec/battery/lamp fault / emergency lighting test failed)
0 = State unknown
1 = No faults present
2 = At least one fault present
3 = Reserved, no function
Group object name
Output A - Emergency light x
Data type
Flags
2 byte
C, R, T
DPT_CS