Commissioning
82 2CDC507164D0201 | DG/S x.64.1.1
Dimming time (0 = jump to)
Options:
0...2...65,535 s
This parameter can be used to set a soft start by defining how long the output takes to dim up from
0% brightness to the turn on brightness when it receives an ON telegram. This time period refers to
ON telegrams only (1 bit).
0 s: Jump to. The output switches ON immediately (DALI ON command).
1...65,535 s: During this time, the output is dimmed from 0% brightness to the turn on
brightness.
Note
When setting dimming times of less than 32 seconds, note that they will be mapped to the
nearest DALI fade time. The conversion is as follows:
Turn on
brightness
in 1 s
0
1
2
3
4
5 and 6
7...9
10...13
14...18
19...26
27...32
> 32...65,535
The fade time is specified as the time required to change the lamp power from the current
brightness value to the required target brightness.
If a lamp is switched off, the preheat and ignition time are excluded from the fade time.
Selection of Can be changed via object "Flexible time for dimming/fade time":
Note – dependency:
Object enabled on "Output functions" page
Fade time in s
acc. to EN 62386-102
jump to
1.0
2.0
2.8
4.0
5.7
8
11.3
16.0
22.6
32.0
Time values with an error tolerance of ±3 s