ABB i-bus KNX Product Manual page 34

Dali-gateway basic dg/s x.64.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
Enable Group object
"In operation"
Options:
Linked group object:
The In operation group object indicates the presence of the DG/S on the KNX. This cyclic telegram can be
monitored by an external device. If a telegram is not received, the device may be defective or the KNX
cable to the transmitting device may be interrupted.
Yes: The group object is enabled.
No: The group object is not enabled.
32 2CDC507164D0201 | DG/S x.64.1.1
Yes
No
Selection of Yes option:
Dependent parameters:
Sending
Options:
Value 0
Value 1
The In operation group object is sent cyclically on the KNX.
Sending cycle time
Options:
1...60...65,535 s
The time interval at which the In operation group object cyclically sends a telegram is set here.
Note
After a bus voltage recovery the group object sends its value after the set inactive wait state
defined in the General parameter window has elapsed.
In operation