ABB i-bus KNX Product Manual page 138

Dali-gateway basic dg/s x.64.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
136 2CDC507164D0201 | DG/S x.64.1.1
Enable additional function
Options:
None
Slave
Staircase lighting
Linked group object:
This parameter defines an additional function for the group or ballast. At the same time, it enables a
corresponding parameter window where the additional function can be parametrized.
None: This group/ballast operates as "normal", without an additional function.
Slave: This group/ballast is defined as a slave. The slave is forcibly controlled by a master.
The Group x Slave parameter window is enabled. This is where the properties of the slave are
parametrized. The slave receives the required brightness value from a master ballast or group
via the Brightness value of slave group object or internally via the gateway itself.
Staircase lighting: When the Staircase lighting function is activated, the group/ballast is
switched on, and after a defined time it is automatically switched off or dimmed down slowly as
an advance warning. The staircase lighting function has two levels. The turn off brightness can
be activated/deactivated via the KNX for nighttime operation.
Activate fct Slave
Activate fct Staircase lighting