ABB i-bus
KNX
Commissioning
Emergency lighting converter reacts on
object "Inhibit/rest mode"
Options:
Yes: The Activate emergency lighting Inhibit/rest mode group object is evaluated so that the
emergency lighting converter receives the rest/inhibit command via the gateway.
This means it is possible to deactivate the emergency lighting function so as to conserve the battery
charge e.g. during a construction/commissioning phase.
No: The Activate emergency lighting Inhibit/rest mode group object is not evaluated for the converter.
The mode functions cannot be influenced by the gateway.
Note
To use the Rest/inhibit function you first need to enable the output's Activate emergency lighting
Inhibit/rest mode group object in the A lighting converter parameter window. You also need to select the
function for the individual emergency lighting converters.
Note
Rest mode is a state in which the emergency light is switched off during its emergency lighting
operation.
Inhibit mode is a timed state in which the emergency light does not switch to emergency operation in the
event of a mains voltage failure.
In both cases, the emergency light no longer fulfils its safety function and remains off.
For this reason, use this function with great care. It can be helpful to use Inhibit/rest mode during the
construction phase when the power supply is often switched off, to prevent the emergency lighting
battery from constantly charging/discharging and thus conserve the emergency light.
Yes
No
Danger
DG/S x.64.1.1 | 2CDC507164D0201 159