ABB i-bus KNX Product Manual page 52

Dali-gateway basic dg/s x.64.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
50 2CDC507164D0201 | DG/S x.64.1.1
Selection of Fixed fade time option:
Dependent parameters:
Dimming time (0 = jump to)
Options:
0...2...65,535 s
This parameter defines how long it takes to dim up to the set brightness value. This time only
relates to the output's Brightness value telegram (8-bit).
0 s: Jump to. The output immediately switches to the brightness value.
1...65,535 s: During this time, the output is dimmed up to the brightness value.
Note
When setting dimming times of less than 32 seconds, note that they will be mapped to the
nearest DALI fade time. The conversion is as follows:
Turn on
brightness
in 1 s
0
1
2
3
4
5 and 6
7...9
10...13
14...18
19...26
27...32
> 32...65,535
The fade time is specified as the time required to change the lamp power from the current
brightness value to the required target brightness.
If a lamp is switched off, the preheat and ignition time are excluded from the fade time.
Selection of Can be changed via object "Flexible time for dimming/fade time":
Note – dependency:
Object enabled on "Output functions" page
Fade time in s
acc. to EN 62386-102
jump to
1.0
2.0
2.8
4.0
5.7
8
11.3
16.0
22.6
32.0
Time values with an error tolerance of ±3 s