ABB i-bus KNX Product Manual page 48

Dali-gateway basic dg/s x.64.1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
Dim period to reach turn off
brightness
Options:
This group object defines whether the dimming time can be changed via KNX.
Fixed fade time: Dimming time is permanently set and cannot be changed via the KNX.
Can be changed via object "Flexible time for dimming/fade time": Dimming time can be changed via
the KNX using the Flexible time for dimming/fade time group object.
Note
Flexible dimming time is received via the Output x Flexible time for dimming/fade time group object and
affects various output functions:
To use the Flexible dimming time function you first need to enable the output's Flexible time for
dimming/fade time group object in the A Output/Functions parameter window. You also need to select
the function for the parameter that can be changed via KNX. We recommend that you only change one
time via KNX. Otherwise the dimming time has to be rewritten on the ballast every time a function is
called, which impairs function performance.
46 2CDC507164D0201 | DG/S x.64.1.1
Fixed fade time
Can be changed via object "Flexible
time for dimming/fade time"
Dimming time for turn on/off value
Dimming time for brightness value
Dimming time for slave brightness value
Scene transition time
Selection of Fixed fade time option:
Dependent parameters:
Dimming time (0 = jump to)
Options:
0...2...65,535 s
This parameter can be used to set a soft stop. This defines how long it takes for the output to switch
off from the current brightness on receipt of an OFF telegram. The dimming time still applies even if
the Turn off brightness function is parametrized.
0 s: Jump to. The output switches immediately, either OFF or to the turn off value.
1...65,535 s: During this time, the output is dimmed to OFF or to the turn off value.