ABB i-bus
KNX
Commissioning
Source (slave is controlled via)
Options:
This parameter defines whether the Slave receives its brightness value via the Brightness value of slave
group object via KNX from another KNX device (e.g. a presence detector with a controller function) or
internally, directly from a ballast or group on the output.
Object "slave brightness value"
Group 1
...
Group 16
Ballast 1
...
Ballast 64
Object "slave brightness value": The slave group/ballast receives its brightness value via the
Brightness value of slave group object. In this case, the master is another KNX device. This allows
groups or ballasts on the gateway to be integrated into constant light control for example.
Group x: The slave group/ballast receives its brightness value internally from group x.
No KNX communication connection is required for this.
Ballast x: The slave group/ballast receives its brightness value internally from ballast x.
No KNX communication connection is required for this.