ABB i-bus
KNX
Commissioning
No.
44
This group object is enabled if the Enable function Inhibit/rest mode object "Activate Inhibit/rest mode" parameter is set to Yes
in the X lighting converter parameter window, p. 149.
This group object activates or deactivates the Inhibit/rest mode function for an emergency lighting converter.
Whether the converter evaluates and reacts to the Activate Inhibit/rest mode group object is defined for each converter in the
A lighting converter/Emergency light x parameter window.
Telegram value:
44
This group object is enabled if the Enable function Inhibit/rest mode object "Activate Inhibit/rest mode" and Send status
Inhibit/rest mode parameters are both set to Yes in X lighting converter parameter window, p. 149.
This group object has the same function as Activate Inhibit/rest mode. In addition, it provides the status of Inhibit/rest mode on
the KNX.
Telegram value:
198 2CDC507164D0201 | DG/S x.64.1.1
Function
Activate emergency lighting
Inhibit/rest mode
Dependent on parameter
1 = Inhibit/rest mode is activated. In the event of a mains voltage failure the emergency light does not
switch to emergency operation, and if it is already in this mode when Inhibit/rest mode is activated, it
exits emergency operation.
0 = Inhibit/rest mode is deactivated. The emergency light is in normal mode and switches to emergency
operation in the event of a mains voltage failure.
Caution
Note that when Inhibit/rest mode is activated, the emergency light has no emergency lighting function. In the event
of a mains voltage failure the emergency light stays dark and does not switch to emergency operation.
Note
Rest mode is a state in which the emergency light is switched off during its emergency lighting operation. The
system automatically exits rest mode in the event of a mains voltage failure. The emergency light is then in normal
mode again.
Inhibit mode is a timed emergency lighting converter state in which the emergency light does not switch to
emergency operation in the event of a mains voltage failure. The emergency light remains off. If the emergency
lights are not switched off within 15 minutes (of Inhibit mode being activated), emergency operation is not activated
and the light stays off. The system exits Inhibit mode:
- after 15 minutes unless the Inhibit command is repeated.
- if the mains voltage fails. On mains voltage recovery the emergency light is in normal mode.
- on receipt of DALI command 226 "RE-LIGHT/RESET INHIBIT".
Activate emergency lighting
Inhibit/rest mode/Status
Dependent on parameter
1 = Inhibit/rest mode is activated.
0 = Inhibit/rest mode is deactivated.
Group object name
Output A
Enable function Inhibit/rest mode object "Activate Inhibit/rest mode"
Output A
Send status Inhibit/rest mode
Data type
Flags
1 bit
C, W, T
DPT 1.010
1 bit
C, R, W, T
DPT 1.010