N-Ann-Led Board Layout And Connection To Facp; 7: N-Ann-Rly Relay Module; Specifications - Honeywell NOTIFIER SFP-5UD Series Manual

Fire alarm control panels
Hide thumbs Also See for NOTIFIER SFP-5UD Series:
Table of Contents

Advertisement

Installation

N-ANN-LED Board Layout and Connection to FACP

Figure 2.27 illustrates the N-ANN-LED board wiring connections to the FACP.
TB3
2.8.7 N-ANN-RLY Relay Module
The N-ANN-RLY relay module provides 10 programmable Form-C relays when used with a compatible FACP.

Specifications

Operating Voltage: 24 VDC
Max. Current:
 Alarm: 75 mA
 Standby: 15 mA
Relay Contact Ratings:
 2 amps @ 30 VDC (resistive)
 0.5 amps @ 30 VAC (resistive)
Operating Temperature: 32
For indoor use in a dry location only
46
ANN-BUS (ID#)
Address DIP switch
FACP
-24 VDC
+24 VDC
Primary ANN-BUS
Figure 2.27 N-ANN-LED Board Layout and Connection to FACP